RESIDENTIAL GAS AND ELECTRIC WATER HEATER
TROUBLESHOOTING and SERVICE HANDBOOK
RELIANCE Water Heater Company Technical Training Department
©2006 Ashland City, TN
18
If there has been a flammable vapor ignition, a qualified service agent needs to inspect the arrestor
for cracks. The arrestor is not a replaceable part – the heater would need to be replaced.
Possible service issues associated with the flame arrestor.
Poor combustion – yellow flame, sooting, possible carbon monoxide production.
Pilot outage due to lack of oxygen. Continued pilot outage or finding that the LDO screen(s) is
heavily blocked would warrant inspection of the flame arrestor.
Pilot outage due to increased combustion chamber temperatures below the main burner. This may
open the automatic reset, thermal cut off switch (TCO).
The flame arrestor having contained a flammable vapor ignition. The TCO will open and the
chamber and arrestor should be inspected by a qualified service agent.
COMBUSTION CHAMBER TEMPERATURE SENSOR
The C3 Technology water heaters will come equipped with a thermal cutoff (TCO) device that is
integral with the thermocouple. Temperature cutoff points range from 160°C to 200°C depending on
model. The TCO is an automatic reset thermal switch. When activated it will open the
thermocouple circuit and shut off the main and pilot burner gas flow. The pilot would have to be relit
after the TCO has had sufficient time to cool down (sensor is below 120 degrees F).
The TCO performs two primary functions:
In the event of flammable vapor ignition inside the combustion chamber, it senses the
corresponding increase in temperature and shuts off gas flow to the main and pilot burners.
If excessive temperatures inside the combustion chamber indicate poor combustion due to
a clogged LDO screen or inadequate air for combustion, the TCO will shut off gas flow to
the main and pilot burners.
SERVICE:
There is no routine service associated with the TCO. The standard thermocouple millivolt output checks
described in this service handbook still apply. Millivolt readings indicate that the TCO is closed. An open
TCO (within a cool chamber) would indicate that the assembly must be replaced.