Reliant FVIR GAS WATER HEATER Betriebsanleitung Seite 7

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 28
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 6
7
Installing the water heater
This water heater must be installed in accordance with these instructions, local codes, utility company
requirements, and/or in the absence of local codes, use the latest edition of the American National
Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association,
400 N. Capitol Street NW, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269 as booklet NFPA 54.
Location
The water heater should not be
located in an area where leakage
from the tank or connections will
result in damage to the area adjacent
to the heater or to lower floors of the
structure.
When such areas cannot be avoided
it is recommended that a suitable
catch pan, adequately drained, must
be installed under the water heater.
The pan must not restrict air flow
to the combustion air inlet openings
(perforation openings) located around
the lower perimeter of the water
heater.
Catch pan kits are available from
the store where the water heater
was purchased, or any water heater
distributor.
Make certain the floor underneath
the water heater is strong enough to
sufficiently support the weight of the
water heater once it is filled with water.
A gas fired water heater or any other
appliance should not be installed in
a space where liquids which give off
flammable vapors are to be used or
stored. Such liquids include gasoline,
LP gas (butane or propane), paint or
adhesives and their thinners, solvents
or removers.
When installed in a closet, DO
NOT block or obstruct any of the
combustion air inlet openings located
around the perimeter of the water
heater. A minimum of 1” is required
between these combustion air inlet
openings and any obstruction.
Because of natural air movement
in a room or other enclosed space,
flammable vapors can be carried some
distance from where liquids which give
off flammable vapors are to be used
or stored. The open flame of the water
heaters pilot or main burner can ignite
these vapors and create a shut down
condition of the water heater which
will not allow the water heater to ignite
until examined by a Qualified Service
Technician.
FVIR certified gas water heaters can be
installed on a residential garage floor
without the use of an 18-inch stand in
accordance with the National Fuel Gas
Code, NFPA 54, ANSI Z223.1, unless
otherwise directed by State and Local
code requirements. The water heater
must be located so it is not subject
to physical damage, for example, by
moving vehicles, area flooding, etc.
The water heater should be installed
as close as practical to the gas vent
or chimney.
Long hot water lines should be
insulated to conserve water and
energy.
The water heater and water lines
should be protected from exposure
to freezing temperatures.
DO NOT install the water heater in
bathrooms, bedrooms, any occupied
rooms normally kept closed, or in
unprotected outdoor areas.
Minimum clearance from
Combustible construction:
If the clearances stated on the
Instruction/Warning Label, located on
the front of the heater differ, install
the water heater according to the
clearances stated on the label.
If the water heater is installed in
an alcove or closet, the entire floor
must be covered by a wood or metal
panel.A minimum of 24” clearance
from the front and top should be
available for adequate inspection and
servicing.
The water heater may be installed on
combustible floors, but not directly
on carpeting. If the water heater
must be installed on carpeting, place
a metal or wood panel beneath the
water heater, extending beyond its
full width and depth at least 3” in all
directions.
!
WARNING: Combustible
construction refers to
adjacent walls and ceilings
and should not be confused
with combustible or
flammable products and
materials. Combustible
and/or flammable products
and materials should never
be stored in the vicinity of
this or any gas appliance.
Location Front Sides Rear Top
Alcove
3”
(7.6 cm)
0”
(0 cm)
0”
(0 cm)
12”
(30.5 cm)
Closet
3”
(7.6 cm)
1”
(2.5 cm)
0”
(0 cm)
12”
(30.5 cm)
Rear
Sides
Front Open
Sides
Front Enclosed
Top View Closet
Top View Alcove
Rear
Combustion Air Inlet
Openings
The auxiliary catch pan
installation MUST conform
to local codes.
Diameter of
water heater
plus 2” min.
Max.
2
Seitenansicht 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 27 28

Kommentare zu diesen Handbüchern

Keine Kommentare