RESIDENTIAL GAS AND ELECTRIC WATER HEATER
TROUBLESHOOTING and SERVICE HANDBOOK
RELIANCE Water Heater Company Technical Training Department
©2006 Ashland City, TN
52
Residential Electric – continued
A-7 Voltage Check - continued
Complaint: Lack of Hot Water
Test Conditions:
Upper thermostat satisfied
Test between upper high limit 4 and upper thermostat 4
If … … then
proper voltage is not present replace upper thermostat.
proper voltage is present continue to next step.
Test between lower high limit terminal 1 and 3 or L1 and L3
If … … then
proper voltage is not present check wiring to upper thermostat and
heater junction box.
check that off peak meter is not
“Open”.
proper voltage is present continue to next step.
Test between lower high limit 2 and 4 or L1 and L4
If … … then
proper voltage is not present push lower high limit reset.
pushing reset restored voltage conduct lower thermostat check
conduct lower element checks
pushing reset did not restore voltage replace lower high limit
proper voltage is present continue to next step