RESIDENTIAL GAS AND ELECTRIC WATER HEATER
TROUBLESHOOTING and SERVICE HANDBOOK
RELIANCE Water Heater Company Technical Training Department
©2006 Ashland City, TN
16
IMPLEMENTATION
CATEGORY
ANTICIPATED
INTRODUCTION
CLASS OF PRODUCTS
INCLUDED IN THIS CATEGORY
Phase I July 1, 2003
30, 40, and 50 gallon atmospheric vented. (Manufactured housing
models are excluded.)
Phase II January 1, 2005
30, 40, and 50 gallon power-vented models. (Manufactured housing
models are excluded.)
Phase III July 1, 2005 All other gas-fired models with inputs of 75,000 BTU or less.
This supplement addresses the July1, 2003 compliant products.
In addition to the standard water heater design discussed in the main service handbook, the C3 Technology
design also includes:
A LDO (Lint Dust and Oil) screen over the combustion air intake
A Flame Arrestor
A combustion chamber Thermal Cut Off (TCO) limit
An additional tool for these products might be a vacuum cleaner with both blowing and vacuuming
capabilities. Also include the long, narrow crevasse accessory.
LDO SCREEN (LINT, DUST, OIL) SCREEN(S)
An easy to clean screen designed to minimize lint, dust and oil based contaminants from being drawn into
the “Flame Arrestor” along with make up – combustion - air. There may be one or two of these screens. The
LDO screen must be installed with the arrows on the right and left side facing up to function properly. (The
arrows are located on two mounting tabs on each side of the screen).
Service:
Inspect the LDO screen(s) regularly. Clean or wash as necessary.
Pulling the tab located in the middle of the screen will remove the screen. Reinstall the clean screen by
inserting the end tabs into the jack with the arrows pointing up.
Possible Service issues associated with a blocked screen:
Poor combustion – yellow flame, possible sooting
Pilot outage resulting from a lack of oxygen
Pilot outage resulting from to increased combustion chamber temperature below the main burner.
This may open the automatic reset, thermal cut off switch (TCO).